Connect all EndurEnergy ESP-5100 batteries together with the provided RJ45 cable using “M/S” ports. (Can use up to 8 batteries in 48V low voltage configuration)
Connect a standard CAT5/6 cable to the “Inverter” port on the ESP-5100 Master battery, and the “Battery CAN Bus” port (or the “CAN” port for indoor-only units) on the Sol-Ark.
BMS 00
Program the inverter with this battery's appropriate charge/discharge settings.
Enable “BMS Lithium Batt” and set its value to “00.”
BMS Error Stop Option
If you wish for the system to fault on the loss of battery communications, turn on “BMS_Err_Stop”